I. Product introduction
RVC-Z reactive power compensation controller has 3-phase voltage/current sampling function and allows any combination compensation of Y+△. The other basic technical performances are same as RVC. It can output DC 12V to control contactless switch or connect 220V/380V AC contactor to switch capacitor for reactive compensation. The controller is designed with reactive power/current and comprehensive sampling and the most advanced programmable switching mode (1:1:1:1, 1:2:2:3, 1:2:3:4…………), and allows the automatic selection of split phase or 3-phase preference strategy according to the load condition. It offers the best reactive compensation effect in various conditions and environments. RVC series controllers have powerful function and high interference resistance, can operate normally in network environments with a high THD, and have alarm functions such as high harmonic alarm, RS 232/485 communication interface, MOTBUS communication protocol output.
II. Product model number explanation

III. Programmable parameters
CT transformation ratio: 100-8000 (automatically adapting to the phase alternation on CT side of network)
COSφ target value: inductive: 0.70-1.00; capacitive: 0.70-1.00
C/K value: 0.01-0.99
Y+△ setting: 12+0; 9+3; 6+6; 3+9
THD: 5-40%
Step delay: 1-120s
Max. output ways: 12
Undervoltage value: 300-380
Overvoltage value: 420-460
Sequence type: 1.1.1-1.2.8
Alarm switch: ON/OFF
IV. Alarm and protection function
1. Under current alarm and disconnecting step capacitor
2. Overcurrent alarm
3. Overvoltage alarm and disconnecting step capacitor
4. Undervoltage alarm
5. Low COSФ alarm (lower than COSФ set value when all connected)
6. Abnormal COSФ alarm
7. Capacitance lower than 70 % alarm
8. Alarm at 60℃ and disconnecting step capacitor at 70℃
9. THD lower than set value alarm and disconnecting step capacitor
10. Open-phase protection
V. RVC-Z series control schematic diagram

VI. Technical specifications
1. Operating voltage: 100-440V
2. Frequency range: 50Hz/60Hz ±5%
3. Input current: 0-5A
4. Output voltage: DC 12V or AC 220/380V
5. Output ways: 12
6. Power consumption: <15W
7. Operating temperature: -25℃~+70℃
8. Relevant humidity: max. 95% without condensation
9. Memory function: all parameters and modes are stored in nonvolatile memory
10. Display: current I, voltage U, active power P, reactive power Q
11. Weight: 1.00kg (excluding package)
12. Elevation: ≤3500M
13. Housing dimensions: 144mm×144mm×95mm (L × W × D)
14. Opening size: 138×138mm (L×W)
VII. RVC series product standards
1. GB/T14549-199 Power System Harmonic Management Standard
2. GB/T15576-1995 The specification of low-voltage reactive power steady compensation equipment
3. JB/T9663-1999 Low voltage reactive power automatic compensating controller
4. DL/T597-1996 Low voltage reactive power compensation controller ordering specifications